Product : ISaGRAF V3
Date : 20-May-1999
File : IXL.IXLConnect does not check if appli is running.htm
Subject : IXLConnect does not check if appli is running
Keywords: IXL - Running application
____________________________________________________________________
Remember that IXL is not a documented and supported feature
of ISaGRAF.
the function IXLConnect does not check if appli is running.
To do this test, use the function IXLTestAppTGT( ).
This function is correctly implemented in the sense where it
returns an error while the application is being downloaded.
Except that it uses mutexes and in case of concurrent calls
from multiple threads it could give a wrong return
(i.e. appli is running).
You have to ensure that there are no concurent calls.
Note:
After a successfull connection,
you have to disconnect if there is no application running
____________________________________________________________________